  • Katalog Produk

    PORTABLE PROCESS ANALYZER FOR SULFUR HEXAFLOURIDE, Model : 337 SERIES, Brand : Nova

    Jumlah Pesanan
    Tambah ke Keranjang
    Negara Asal
    Kanada
    Kenalkan ke teman Anda Masukan ke Produk Rekanan

    Keterangan

    APPLICATIONS
    For checking sulfur hexafluoride ( SF6) in blanketing applications for power cable, switch gear and magnesium
    production.

    FEATURES
    • Rugged design that is easy to operate
    • Fast warm up and response
    • Long life thermal conductivity cell that provides accurate and stable readings
    • Digital meter readout with backlight
    • Modular layout that is easy to maintain
    • Rechargeable ' gel cell' battery operated
    • Built in sample pump
    • Lightweight, compact and easy to use
    • Weatherproof ( WP) cabinet with clear lexan cover

    OPTIONS
    • Recorder outputs of 0-1V or 4-20mA
    • Sample pre-cooler for hot samples
    • Condensate removal for wet applications
    • Suitcase ( K) style cabinet available
    • AC power only operation
    • CO2 alarms with LED
    • Datalogger

    CALIBRATION
    • Ambient air for zero
    • Cylinder of analyzed SF6 calibration gas for span.

    DESCRIPTION
    The Nova 337 Portable Process Analyzer has been designed for the detection of sulpur hexaflouride ( SF6)
    primarily in air or nitrogen ( N2) . However it can be used in some other applications with several background
    gases present. Consult Nova on these applications.
    The thermal conductivity ( T/ C) cell provides a fast and accurate measurement of SF6. It has an expected life of over 10 years unless contaminated.
    In operation, a built in sample pump draws in the gas sample through the probe, filters, flow meter, and to the
    T/ C cell. The detected SF6 is displayed on an LCD digital meter which has a switchable back light for use in dark
    areas.
    A rechargeable ' gel cell' battery provides enough power for approximately 8 hours of continuous operation and the analyzer can be used while it is being recharged. A red LED tells when to recharge and a green LED verifies that it is receiving recharging power. The recharger is included.

    SPECIFICATIONS
    Method of Detection: Temperature compensated thermal conductivity ( T/ C) cell cannot be burned out due to loss of flow or changing gases
    Ranges: 0-100% SF6 in air or in N2
    Resolution: ± 0.1% of He
    Accuracy and Repeatability: ± 2% of full scale
    Drift: ± 1% of full scale per week
    Response Time ( T-90) : 10-15 seconds to 90% step change - not including sample transport time
    Ambient Temperature Range: 55° to 120° F ( 12° to 50° C)
    Linearity: ± 2% of F.S. on SF6 in Air
    Size and Weight: WP style - approx. 10" L x 7½ " H x 6½ " D @ 8 lbs ( 25.5 x 19 x 16.5 cm @ 3.6 kg)
    K style approx. 9½ " L x 6½ " H x 7" D @ 8 lbs ( 24 x 16.5 x 18 cm @ 5.5 kg)
    Power: 115VAC 60Hz ( 220VAC 50Hz available)
    Output Options: 4-20 mA or 0-1 VDC